Watts/RMC Model 7F-AUS
Single Detector Check Valve (Dual CV)
This device can be supplied with a water meter in bypass to account for small usage of water. Suitable for dedicated fire lines and combination fire and general service connections.
 
Sizes DN80 to DN250
Hazard Rating Low
Must be registered As per local authority
Standard Nil
Testable Yes, As per local authority
Protection against back pressure and back-siphonage Yes

Testing & Maintenance requirements As per local authority
Pressure & Temperature   Working Pressure: 1400kPa
  Test Pressure: 2000kPa
  Maximum Working Temperature: 70ºC (DN80 - DN250)
Specific Installation Requirements
Not to be located in a corrosive or polluted atmosphere
Insulation or other protection not to interfere with its operation, testing or maintenance
May be located in pits, but not buried in the ground.
Where water hammer occurs downstream, water hammer arrestor to be used.
All devices to be readiliy accessible.
No heat to be applied during installation.
Approved resilient seated isolation valves to be installed immeadiately upstream, adjacent to device.
Pipework to be flushed before connection.
Specification
The single detector check valve shall consist of a single positive seating, centre guided chck assembly. It shall have a field removable seal and seat assembly with an encapsulated spring. Acxcess is through an "O" ring sealed cover secured by stainless steel fasteners. The valve will be fusion bonded, epoxy coated internally and externally.