Watts RMC Model 800
Pressure Vacuum Breaker Device (PVB)
Sizes DN15 - DN50 FOR CONTINUOUS PRESSURE APPLICATION
Hazard Rating Medium
Must be registered Yes
Standard AS2845.1
Testable Yes
Protection against back pressure and back-siphonage? Back-siphonage only

Testing & Maintenance requirements Test after installation prior to service. Maintain in working order and inspect for operational function at intervals not exceeding twelve months. These functions to be carried out by authorised licensed testers.
Pressure & Temperature   Working Pressure: 1400kPa
  Test Pressure: 2000kPa
  Maximum Working Temperature: 60ºC

Specific Installation Requirements
Installation or other protection not to interfere with its operation, testing or maintenance
Drainage from vent port should be readily visible but not as a hazard or nuisance.
In the horizontal plane, vent is to point downwards with 300mm minimum clearance from ground to vent.
Line strainers to be fitted immediately upstream.
Approved resilient seated isolation valves shall be installed immediatly upstream and downstream of the device
To be installed at least 300mm above the highest downstream outlet
Not to be subject to flooding or freezing temperatures.