| Atmospheric Vacuum Breaker Device (AVB) |
| Sizes | DN6 to DN80 | ![]() |
| Hazard Rating | Low | |
| Must be registered | No | |
| Standard | AS2845.1 | |
| Testable | No | |
| Back-siphonage only | Yes |
| Testing & Maintenance requirements | No testing required Check regulatory Authority requirement |
| Pressure & Temperature |
| Specific Installation Requirements |
| To be located at least DN150 above the highest downstream outlet | |
| No isolating valves to be fitted downstream of device | |
| Under normal circumstances, not to remain under continuous pressure for more that 12 hours | |
| To be vented to atmosphere at all times | |
| Not to be subject to flooding |